Scheduled Maintenance
[DC3] Thermography checks

Thermography checks

Location : DC3

What is done : As part of annual checks, we will do a thermography on the datacenter 'DC3'. To minimize risks, this thermography will be realized cabinet by cabinet.

Impact : None.

Start : 18-Nov-2019 0600Z 0800LT

Duration : 6 days.

SCW - Hypervisors Upgrade

[PAR1, AMS1] BIOS and kernel upgrade on DEV1 and GP1 hypervisors

Location : PAR1, AMS1

What is done : We are about to upgrade our DEV1 & GP1 hypervisors. The operation will reboot the virtual machine and takes several minutes of downtime. Network configuration will be maintained but connectivity is lost during the reboot.

implement kernel upstream changes committed by Scaleway contributors for new upcoming features, implement vendor BIOS upgrade to fix major availability issues and improve performances of our DBaaS product, implement Ubuntu bugfix to the snapshot functionality to improve reliability of snapshots. Impact : 20 minutes downtime (per hypervisor)

Email notification will be sent and it will be providing more details about the expected time of downtime per hypervisor.

Duration : 7 Days on Paris region & 5 days on Amsterdam region

Start : 18-Nov-2019 1000Z 1200LT (Paris)
Start : 18-Nov-2019 1000Z 1300LT (Amsterdam)
End : 26-Nov-2019 1600Z 1800LT (Paris)
End : 22-Nov-2019 1200Z 1400LT (Amsterdam)
[RPN] DC3 >< AMS1 - SIPARTECH Network update

SIPARTECH is doing a maintenance on the network.

Location : DC3/AMS1

What is done : preventive network maintenance

Impact : RPN Service will be unavailable

Start : 18-Nov-2019 2259Z 2359LT

Duration : 6 hours.

[DC3] Maintenance of HV Stations DATA 2, A/C/F1 and B/D/F2 + transformer TR F1

[DC3] Maintenance of HV Stations DATA 2, A/C/F1 and B/D/F2 + transformer TR F1

The planned preventive maintenance consists of :

-maintenance of HV cells on delivery station “DATA2”and sub-station “B/D/F2”and electrical protection tests.

-Replacement of relay DMCR on transformer TR F1The entire electrical load of DC3 is supplied from “DATA1” delivery station.

The “DATA2” delivery station does not supply any load in normal operation mode. Its switching off for this operation will not have any impact on the datacenter electrical supply. The maintenance of HV sub-station and transformer F1 will be realized while the load is supplied by generators.

Impact : This intervention does not present any particular risk of service interruption and will be processed during working hours

Start : 19-Nov-2019 0700Z 0800LT

Duration : 10 Hours

[DC3] Maintenance of HV stations DATA 1

[DC3] Maintenance of HV stations DATA 1

The planned preventive maintenance consists of the maintenance of HV cells and electrical protection tests on delivery station “DATA1”. The electric chains will be supplied from generators during this maintenance.

Impact : This intervention does not present any particular risk of service interruption and will be processed during working hours

Start : 21-Nov-2019 0700Z 0800LT

Duration : 10 hours

[DC3] Maintenance of fire suppression system

[DC3] Maintenance of fire suppression system

Maintenances:

-Control VESDA system

-Control manual triggers

-Control of sound and visual alarms

-Control Actuated Devices of Safety

-Control alarm reports

-Controle valves fire suppression (outside datarooms)

-Control smoke extraction and extraction engine.

Impact : No impact for customers

Start : 9-Dec-2019 0500Z 0600LT

Duration : 14 Days

[DC3] - Curative maintenance on battery of UPS

[Curative maintenance on battery of UPS]

We will do the curative maintenance of the inverter of electrical chain A. Operations will be performed by our maintainer under our permanent supervision. The downtime of an UPS is estimated to take 30 minutes.

The operation will be done by UPS and will have no impact on your equipments housed in our Datacenter.

Location : DC3 DATACENTER

Impact : None

Start : 11-Dec-2019 0730Z 0930LT
End : 11-Dec-2019 1530Z 1730LT

Duration : 1 day

Past Incidents

Sunday 17th November 2019

No incidents reported

Saturday 16th November 2019

No incidents reported

Friday 15th November 2019

Dedibackup Dedibackup delivery issue

Dedibackup storage delivery can't currently be done. We are working on a fix. Dedibackups currently in function are not affected by this.

===================

15/12/2019 1730Z (1830LT)

The product team has identified the root cause and working on a fix

DC2 DC2 - Room 205 - Dedicated Server's installation

We are currently facing issue with ongoing installation on DC2 room 205.

Your installation might not go through. We are currently investigating on this matter.

===================

15/11/19 1145Z (1245LT)

Issue has been escalated to local team

15/11/19 1330Z (1430LT)

The incident is now over

Thursday 14th November 2019

No incidents reported

Wednesday 13th November 2019

DC3 Power issue in DC3 Room 3-5 rack A11

We are currently expecting a power issue in DC3, Room 3-5, Rack A11. Team in charge is already investigating to solve it as soon as possible.

===================

11.13.19 1820Z (1920LT)

Issue is solved and impacted servers are functional again.

11.13.19 1745Z (1845LT)

Issue has been escalated to local team

DC3 Power problem on DC3 Rooms 3-2-A2, 3-2-A3

We are currently encountering a power problem on 2 racks in the room: 3-2

Our teams are fully mobilized to solve the problem.

Location : DC3: Room 3-2-A2, 3-2-A3

Impact : The connection and access to the server can be interrupted.

Start : 13-Nov-2019 1408Z 1508LT
End : 13-Nov-2019 1442Z 1542LT

DC3 Power problem on DC3 Rooms 3-2, 3-5, 4-5

We are currently encountering a power problem in the rooms: 3-2, 3-5, 4-5 Our teams are fully mobilized to solve the problem.

Location : DC3: Room 3-2, 3-5, 4-5

Impact : The connection and access to the server can be interrupted.

Start : 13-Nov-2019 0838Z 1038LT
UPADTE : 13-Nov-2019 1016Z 1116LT

All servers are now up and reachable. The incident is now over.

Tuesday 12th November 2019

No incidents reported

Monday 11th November 2019

No incidents reported