Scheduled Maintenance
DC3 Curative maintenance on PLC SSA and SSB

[DATACENTER DC-3] Curative maintenance on PLC SSA and SSB

A modification will be done on PLC SSA and SSB to increase the delay y during the weekly switching of chillers.Installations will be switched to manual mode during the maintenance of the PLC.

Impact : No impact on customers or services

Start : 22-Oct-2019 0600Z 0800LT

Duration : 10 hours

DC5 - Load tests of generators

Location : DC5

What is done : We will perform the data center's redundancy test. Operations will be performed by our maintainer under our permanent supervision, according to the following provisional schedule:

Thursday, October 24th: 0800 AM

Thursday, October 24th: 14PM

Impact : no impact for customers

Start : 24-Oct-2019 0600Z 0800LT

Duration : 6 hours

RPN AMS1/DC3

Upgrade over the RPN network between AMS1 and DC3

Network supplier must perform maintenance on his Network. Maintenance window is from October 26th, 2019 at 10:00 pm UTC to October 27th, 2019 at 4:00 am UTC. The expected Impact length is 6 hours at the maximum, during the maintenance window

Impact : Downtime on the rpn network between AMS1 and DC3

Start : 26-Oct-2018 2200Z 0000LT

It will last : 6 hours

DC3 - Semi-annual maintenance of distribution pumps

DC3 - Maintenance of distribution pumps

Location : DC3 Substation-A, Substation-B, Substation-C

What is done : We will perform the semi-annual maintenance of the distribution pumps. Operations will be performed by our maintainer under our permanent supervision, according to the following previsional schedule:

Wednesday November 6th: Sub-station A

Thursday November 7th Sub-station B

Friday November 8th Sub-station C

Substations A and B supply the chilled water network of the computer halls. Substation C supplies the chilled water network of the operators halls and the air handing units.

Impact : no impact for customers

Start : 6-Nov-2019 0700Z 0900LT

Duration : 3 Days

DC3 - Preventive maintenance of air-handling units

DC3 - Preventive maintenance of air handling units

Location : DC3

What is done : preventive maintenance of air handling units will be performed on the whole site.

Thursday November 12th: Room 01 and 02

Wednesday November 13th: Room 03 and 04

Thursday November 14th: TGBT A and B

Friday November 15th: TGBT C and D

Monday November 18th: TGBT F1 and F2

Impact : loss of redundancy during the preventive maintenance of a TGBT air handling unit. No impact on TGBT cooling.

Start : 12-Nov-2019 0700Z 0900LT

Duration : 5 Days

[DC3] Load shaving tests

[DC3] Load shaving tests

Location : DC3

What is done : As part of the load shaving commissioning on the Datacenter, we will proceed to a test of operation on some generators

Impact : This intervention does not present any particular risk of service interruption.

Start : 13-Nov-2010 0700Z 0900LT

Duration : 7 hours

[DC3] Thermography checks

Thermography checks

Location : DC3

What is done : As part of annual checks, we will do a thermography on the datacenter 'DC3'. To minimize risks, this thermography will be realized cabinet by cabinet.

Impact : None.

Start : 18-Nov-2019 0600Z 0800LT

Duration : 6 days.

Past Incidents

Thursday 10th October 2019

[DC2] Room 203-A - Zone 203-A - Rack N4 - Maintenance, scheduled 1 week ago

Optical fiber replacement.

Location : DC2 Room 203-A - Zone 203-A - Rack N4

What is done : The optic needs to be replaced.

Impact : Service unavailable

Start : 10-Oct-2019 0700Z 0900LT

Duration : overall operation 30min, service downtime 5minutes

Wednesday 9th October 2019

No incidents reported

Tuesday 8th October 2019

No incidents reported

Monday 7th October 2019

No incidents reported

Sunday 6th October 2019

Dedibackup [DC2/DC3] Dedibackup access unavailable

We are currently experiencing an issue with our Dedibackup service on DC2 and DC3.
The access is not available at this moment.

10.07.19 830Z (1030LT)

One of our machines lacked RAM. The problem is now fixed.

===================

10.06.19 1330Z (1530LT)

Issue has been escalated to local team

[WEBHOSTING MAIL] - Mail receiving delay

We have detected mail reception delays and some errors on our webmail for certain webhosting related mail addresses.

We are currently investigating.

===================

10.07.19 1645Z (1845LT)

Webmail access has been fixed.

10.07.19 1600Z (1800LT)

Webmail access has been suspended to help the emails locked to be sent.

10.07.19 7000Z (9000LT)

Mailing team is currently working on the platform having troubles. We are looking for a quick fix to restore access on reception and fix latent issue Mails are in a queue and there will be no mail loss, it will be processed once access is restored

10.06.19 0930Z (1130LT)

Issue has been escalated to local team

Saturday 5th October 2019

No incidents reported

Friday 4th October 2019

[Webhosting] Webhosting platform maintenance, scheduled 1 week ago

[Webhosting] Webhosting platform maintenance

A drive needs to be replaced in one of our webhosting platforms to ensure optimal working conditions.

Impact: Some downtime is to be expected for some of our webhosting customers.

Start: 04-Oct-2019 1400Z (1600LT)
End: 04-Oct-2019 1429Z (1629LT)

Duration : 10 minutes

Console [SCALEWAY] 502 Error

Momentary 502 errors on Scaleway

===================

04/10/19 1245Z (1445LT)

The product team has identified the root cause and fixed it

Cache issues may remain

Dedibackup [Dedibackup] Delivery issues

We have noticed issues with the Dedibackup platform, and new Dedibackup FTP spaces are currently not being delivered.

===================

10.04.19 1606Z (1806LT)

Issue with Dedibackup has been fixed

10.04.19 1345Z (1545LT)

Issue has been escalated to local team

Global Backbone Routing issue through one of our network provider

For a few minutes, one of our network provider faced issues in their network, causing packet losses and traffic drops at multiple destinations.
Issue has now been fixed and traffic should be stable again.

Should you still experience issues, please get in touch with our support team by ticket.

Thursday 3rd October 2019

[Webhosting] Webhosting platform maintenance, scheduled 2 weeks ago

[Webhosting] Webhosting platform maintenance

A drive needs to be replaced in one of our webhosting platforms to ensure optimal working conditions.

Impact : Some downtime is to be expected for some of our webhosting customers.

Start: 03-Oct-2019 1400Z (1600LT)
End: 03-Oct-2019 1420Z (1620LT)